Multi-tier industrial switchboards for centralized motor control, protection and plant automation
NPE designs, fabricates and tests Motor Control Centres (MCCs) in our Nairobi facility to IEC 61439-1 & 2 standards. Our MCC lineups centralize motor starting, power distribution, energy metering, and process interlocking in heavy-duty cubicles engineered for the most demanding agro-processing, chemical, and water utility installations.
Available in Form 2b, Form 3b, and Form 4b internal segregation, each starter compartment is segregated to isolate electrical faults and enable maintenance on individual feeders without interrupting adjacent running processes.
Form 4b • Withdrawable / Fixed
Compartmentalized cubicle switchboard featuring fully isolated busbar chambers, separate cabling compartments, and intelligent motor protection relays.
Lovato Electric • Feeder Protection
High-breaking capacity motor circuit breakers with thermal-magnetic trip units, phase failure sensitivity, and rotary handle mechanisms.
Lovato ADXL • Soft Starter Buckets
Integrated starter modules equipped with Lovato ADXL two-phase soft starters, internal bypass contactors, and Modbus communications.
| Parameter | Specification Details |
|---|---|
| Compliance Standards | IEC 61439-1 & 2, BS EN 61439-1/2, IEC 60947 |
| Rated Main Busbar Current | 630 A, 1250 A, 1600 A, 2500 A, 3200 A |
| Busbar Material | High-conductivity tin-plated copper (ETP Grade C101) |
| Short-Circuit Withstand | 35 kA, 50 kA, 65 kA for 1 second |
| Forms of Separation | Form 2b, Form 3b, Form 4a, Form 4b (Type 2 to 7) |
| Sheet Steel Gauge | 2.0 mm structural frame, 1.5 mm doors and barriers (RAL 7035) |
Send your motor lists, SLDs, and control specifications for a comprehensive MCC proposal.