+254 737 944 014 sales@nairobipower.co.ke
NPE East Africa
HomeAboutServicesProductsSectorsProjectsToolsContact

Motor Control Centres (MCC)

Multi-tier industrial switchboards for centralized motor control, protection and plant automation

Overview

Engineered Motor Control Centres

NPE designs, fabricates and tests Motor Control Centres (MCCs) in our Nairobi facility to IEC 61439-1 & 2 standards. Our MCC lineups centralize motor starting, power distribution, energy metering, and process interlocking in heavy-duty cubicles engineered for the most demanding agro-processing, chemical, and water utility installations.

Available in Form 2b, Form 3b, and Form 4b internal segregation, each starter compartment is segregated to isolate electrical faults and enable maintenance on individual feeders without interrupting adjacent running processes.

Product Lineup

Equipment & Range Highlights

Form 4b Multi-Tier MCC Lineup Form 4b • Withdrawable / Fixed

Form 4b Multi-Tier MCC Lineup

Compartmentalized cubicle switchboard featuring fully isolated busbar chambers, separate cabling compartments, and intelligent motor protection relays.

BusbarHDHC Copper to 3200 A
Fault Rating50 kA / 1s ASTA
SeparationForm 4b Type 6/7
Lovato SM1 / SM2 Motor Protection Breakers Lovato Electric • Feeder Protection

Lovato SM1 / SM2 Motor Protection Breakers

High-breaking capacity motor circuit breakers with thermal-magnetic trip units, phase failure sensitivity, and rotary handle mechanisms.

Current0.1 A – 100 A
Icu @ 400VUp to 100 kA
CoordinationType 2 Tested
Intelligent Soft Starter Starter Buckets Lovato ADXL • Soft Starter Buckets

Intelligent Soft Starter Starter Buckets

Integrated starter modules equipped with Lovato ADXL two-phase soft starters, internal bypass contactors, and Modbus communications.

Capacity18 A – 320 A
BypassIntegrated Internal
ProgrammingNFC / Display
Technical Parameters

MCC Engineering Specifications

ParameterSpecification Details
Compliance StandardsIEC 61439-1 & 2, BS EN 61439-1/2, IEC 60947
Rated Main Busbar Current630 A, 1250 A, 1600 A, 2500 A, 3200 A
Busbar MaterialHigh-conductivity tin-plated copper (ETP Grade C101)
Short-Circuit Withstand35 kA, 50 kA, 65 kA for 1 second
Forms of SeparationForm 2b, Form 3b, Form 4a, Form 4b (Type 2 to 7)
Sheet Steel Gauge2.0 mm structural frame, 1.5 mm doors and barriers (RAL 7035)
Key Features

Engineering & Build Highlights

  • Modular vertical sections with individual starter compartment doors interlocked with isolators
  • Dedicated top or bottom cable entry compartments with generous spreaders for SWA cables
  • Type 2 coordination between circuit breakers, contactors, and overload relays
  • Integrated Lovato DMG series multi-function power meters on incoming and key outgoing feeders
  • Thermographic inspection viewing windows available for predictive maintenance
  • Anti-condensation space heaters with adjustable humidistats for tropical environments
Applications

Target Applications & Sectors

Sugar mills & agricultural processing factoriesWater extraction & municipal wastewater plantsCement, aggregate & mining processing plantsCommercial high-rise HVAC cooling tower loopsEdible oil & beverage bottling plantsPulp, paper & packaging facilities
FAQs
Type 2 coordination guarantees that following a short-circuit fault, the contactor and overload relay suffer no damage and can immediately return to service without component replacement.
Yes. We engineer back-to-back, L-shaped, and front-access-only MCC configurations with bespoke heights and cable box orientations to fit existing plantroom constraints.

Consult with our MCC Design Engineers

Send your motor lists, SLDs, and control specifications for a comprehensive MCC proposal.

Discuss Your Requirement