Motor starting current
Estimate motor current and explore a starting-current multiplier. Use nameplate and manufacturer data for the actual motor.
Enable JavaScript for live calculations. Read the method and default example below.
Method and assumptions
- Running current = shaft kW × 1000 / (supply factor × voltage × power factor × efficiency).
- Starting current = estimated running current × entered multiplier. The method selection does not silently change this assumption.
Before using the result
- This does not predict acceleration, torque, voltage dip or starter compatibility. Verify nameplate current, motor connection and protection coordination.
Worked example
Illustrative default inputs. Enter your project values above.
- Motor shaft power
- 55 kW
- Supply voltage
- 415 V
- Supply arrangement
- Three phase — balanced
- Starting method
- Direct on line
- Motor efficiency
- 92 %
- Running power factor
- 0.86
- Starting-current multiplier
- 6 × running current
Default results
- Estimated running current
- 96.7 A
- Starting-current scenario
- 580.3 A
- Entered multiplier
- 6 ×