ENGINEERED IN NAIROBI. WORKING ACROSS EAST AFRICA.

Motor starting current

Estimate motor current and explore a starting-current multiplier. Use nameplate and manufacturer data for the actual motor.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • Running current = shaft kW × 1000 / (supply factor × voltage × power factor × efficiency).
  • Starting current = estimated running current × entered multiplier. The method selection does not silently change this assumption.

Before using the result

  • This does not predict acceleration, torque, voltage dip or starter compatibility. Verify nameplate current, motor connection and protection coordination.

Worked example

Illustrative default inputs. Enter your project values above.

Motor shaft power
55 kW
Supply voltage
415 V
Supply arrangement
Three phase — balanced
Starting method
Direct on line
Motor efficiency
92 %
Running power factor
0.86
Starting-current multiplier
6 × running current

Default results

Estimated running current
96.7 A
Starting-current scenario
580.3 A
Entered multiplier
6 ×

Choose a reference or send your BOQ

Compare relevant product families, then confirm the exact rating, control supply and duty. Price and availability are confirmed with your enquiry.

Send a BOQ for quotationDiscuss the application

Technical references

These references support planning. The exact model documentation and a project-specific engineering review govern the final specification.