Solar PV sizing

Budget PV modules, storage and AC inverter capacity separately using site yield and simultaneous peak demand.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • PV target = daily kWh / (peak sun hours × net energy yield factor).
  • Storage = daily energy × autonomy / usable fraction. Zero autonomy means no storage budget.
  • Inverter AC kVA = peak AC kW × (1 + reserve / 100) / load power factor. It is calculated separately from PV DC kWp.

Before using the result

  • Not a string, MPPT or protection design. Check site shading, seasonal yield, inverter DC limits, surge duty, battery conversion losses and manufacturer compatibility.

Worked example

Illustrative default inputs. Enter your project values above.

Simultaneous peak AC load
5 kW
AC load power factor
0.9
Daily consumption
12 kWh
Site peak sun hours
5.5 h/day
Net energy yield factor
0.78
Module rating
550 Wp
Storage autonomy
1 days
Supply arrangement
Single phase / two-wire load
Storage chemistry
Lithium
Usable storage fraction
85 %
AC inverter reserve
20 %

Default results

PV array energy target
2.8 kWp
Module count
6
AC inverter capacity budget
6.67 kVA

Choose a reference or send your BOQ

Compare relevant product families, then confirm the exact rating, control supply and duty. Price and availability are confirmed with your enquiry.

Send a BOQ for quotationDiscuss the application

Technical references

These references support planning. The exact model documentation and a project-specific engineering review govern the final specification.