Estimate neutral current from identical, coherent third harmonics on three balanced phases.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • I3 = I1 × third harmonic % / 100; IN3 = 3 × I3; phase RMS = √(I1² + I3²).

Before using the result

  • Balanced fundamentals and identical coherent third harmonics only. Other triplen harmonics, imbalance and frequency-dependent losses are excluded.
  • This does not select neutral conductor size. Use measured spectra and the applicable cable method.

Worked example

Illustrative default inputs. Enter your project values above.

Fundamental current per phase
100 A
Third harmonic relative to fundamental
40 %

Default results

Third harmonic per phase
40 A
Third-harmonic neutral current
120 A
Phase RMS in this model
107.7 A