Lighting lumen method

Estimate luminaire quantity and connected load using photometric utilisation and maintenance factors you enter.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • N = ceil(target lux × area / (lumens per luminaire × utilisation factor × maintenance factor)).
  • Three-phase current assumes evenly distributed luminaires. Select the actual supply arrangement and voltage.

Before using the result

  • Average illuminance estimate only. Verify layout, uniformity, glare, emergency lighting and photometric performance separately.

Worked example

Illustrative default inputs. Enter your project values above.

Room length
12 m
Room width
8 m
Height above work plane
2.2 m
Target average illuminance
500 lux
Lumens per luminaire
4000 lm
Input power per luminaire
36 W
Utilisation factor
0.6
Maintenance factor
0.8
Luminaire power factor
0.9
Supply arrangement
Single phase / two-wire load
Supply voltage
230 V

Default results

Luminaires required
25
Connected input power
900 W
Estimated circuit current
4.35 A