Standby generator sizing

Budget steady-state generator capacity using simultaneous demand, reserve and the manufacturer site-capacity factor.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • Capacity = simultaneous load × (1 + reserve / 100) / (power factor × site-capacity factor).
  • Voltage is across the load for single phase and line-to-line for three phase.

Before using the result

  • Steady-state budget only. Motor starts, load steps, nonlinear loads, permissible voltage/frequency dip and set duty must be checked with the generator manufacturer. No set or ATS model is selected.

Worked example

Illustrative default inputs. Enter your project values above.

Connected load
250 kW
Supply arrangement
Three phase — balanced
Supply voltage
415 V
Load power factor
0.8
Simultaneous load
80 %
Largest motor within connected load
30 kW
Planning reserve
20 %
Manufacturer site-capacity factor
1

Default results

Steady-load capacity budget
300 kVA
Active-power capacity budget
240 kW
Current at entered voltage
417.4 A

Choose a reference or send your BOQ

Compare relevant product families, then confirm the exact rating, control supply and duty. Price and availability are confirmed with your enquiry.

Send a BOQ for quotationDiscuss the application

Technical references

These references support planning. The exact model documentation and a project-specific engineering review govern the final specification.