Earthing conductor

Calculate a protective conductor thermal minimum using the applicable material, insulation and initial-temperature assumption.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • S = I × √t / k. The k value depends on the entered arrangement, material and insulation.
  • This is a thermal minimum; mechanical minimums, PEN requirements, bonding rules, fault-loop impedance and electrode design need separate checks.

Before using the result

  • Use actual protective-device let-through energy where applicable. Confirm that the assumed fault current and disconnection time describe the same fault condition.

Worked example

Illustrative default inputs. Enter your project values above.

Fault current
12000 A
Disconnection time
0.5 s
Conductor material
Copper
Insulation
XLPE — 90 °C
Protective conductor arrangement
Inside multicore cable
Earthing system
TN-S

Default results

Adiabatic minimum
59.34 mm²
Tabulated size candidate
70 mm²
Material constant (k)
143

Choose a reference or send your BOQ

Compare relevant product families, then confirm the exact rating, control supply and duty. Price and availability are confirmed with your enquiry.

Send a BOQ for quotationDiscuss the application

Technical references

These references support planning. The exact model documentation and a project-specific engineering review govern the final specification.