Development demand scenario
Explore a development load using explicit unit simultaneity, common services and future allowance.
Enable JavaScript for live calculations. Read the method and default example below.
Method and assumptions
- Common services are added after unit simultaneity, without further diversity.
- User-entered simultaneity is a scenario assumption, not a regulatory coefficient.
Before using the result
- Verify phase balance, utility requirements, actual load schedules and protective-device design.
Worked example
Illustrative default inputs. Enter your project values above.
- Number of units
- 20
- Connected load per unit
- 5 kW
- Unit simultaneity
- 60 %
- Common services demand
- 15 kW
- Future allowance
- 20 %
- Power factor
- 0.9
- Three-phase voltage
- 415 V
Default results
- Present demand
- 75 kW
- With future allowance
- 100 kVA
- Balanced line current
- 139.12 A