CT secondary burden
Compare complete lead-loop and connected device burden with the CT rated burden.
Enable JavaScript for live calculations. Read the method and default example below.
Method and assumptions
- Lead VA = secondary current² × complete lead-loop resistance. Total external VA = lead VA + device VA.
- Loop resistance includes outgoing and return leads. CT winding resistance is excluded.
Before using the result
- This budget does not verify accuracy, saturation, protection class or performance at the actual operating burden.
- Never open an energised CT secondary. Use an approved shorting and test arrangement.
Worked example
Illustrative default inputs. Enter your project values above.
- CT secondary current
- 5 A
- Complete lead-loop resistance
- 0.113 Ω
- Connected device burden
- 0.5 VA
- CT rated burden
- 5 VA
Default results
- Lead burden
- 2.825 VA
- Total external burden
- 3.325 VA
- Rated burden used
- 66.5 %