Compare complete lead-loop and connected device burden with the CT rated burden.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • Lead VA = secondary current² × complete lead-loop resistance. Total external VA = lead VA + device VA.
  • Loop resistance includes outgoing and return leads. CT winding resistance is excluded.

Before using the result

  • This budget does not verify accuracy, saturation, protection class or performance at the actual operating burden.
  • Never open an energised CT secondary. Use an approved shorting and test arrangement.

Worked example

Illustrative default inputs. Enter your project values above.

CT secondary current
5 A
Complete lead-loop resistance
0.113 Ω
Connected device burden
0.5 VA
CT rated burden
5 VA

Default results

Lead burden
2.825 VA
Total external burden
3.325 VA
Rated burden used
66.5 %