Cable sizing

Compare a protective-device rating with corrected cable capacity for the installation method you enter.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • Source table: G21; method clipped; cu; xlpe.
  • Base temperatures: 30 °C in air, 20 °C in ground. Combined correction factor: 1.
  • Uses the smallest available tabulated size satisfying Ib ≤ In ≤ Iz. Unavailable table cells are skipped.

Before using the result

  • Check actual cable data, termination temperature limits, voltage drop, fault energy, disconnection time and harmonics before specifying. This table does not verify gland dimensions, support spacing or protection coordination.