Busbar sizing

Estimate conductor area from a current-density assumption. Assembly temperature rise and fault strength need separate verification.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • Area = current / assumed current density.
  • Geometry, cooling, enclosure, joints, spacing, neutral harmonics and parallel-bar sharing are not modelled.

Before using the result

  • No temperature-rise rating, bar arrangement or support spacing is certified by this calculation. Verify the actual assembly thermal and short-circuit performance.

Worked example

Illustrative default inputs. Enter your project values above.

Continuous current
800 A
Conductor material
Copper
Assumed current density
1.2 A/mm²
Arrangement
Three phase + neutral

Default results

Area per current-carrying path
666.7 mm²
Entered current density
1.2 A/mm²
Assembly verification
Required before selection

Choose a reference or send your BOQ

Compare relevant product families, then confirm the exact rating, control supply and duty. Price and availability are confirmed with your enquiry.