Voltage drop
Estimate feeder voltage drop from resistance, reactance and power factor, using your chosen voltage-drop limit.
Enable JavaScript for live calculations. Read the method and default example below.
Method and assumptions
- ΔV = √3 × I × L × (R cosφ + X sinφ). L is one-way length.
- Indicative hot conductor resistivity: 0.02193 Ω·mm²/m; R = 0.4386 Ω/km; X = 0.08 Ω/km.
- Maximum length at the entered limit: 231 m.
Before using the result
- Use manufacturer resistance and reactance for final design. The entered supply voltage must match the phase arrangement; this estimate does not cover starting transients or unbalanced circuits.
Worked example
Illustrative default inputs. Enter your project values above.
- Load current
- 100 A
- One-way cable length
- 60 m
- Conductor size
- 50 mm²
- Supply voltage
- 415 V
- Supply arrangement
- Three phase — balanced
- Conductor material
- Copper
- Insulation
- XLPE — 90 °C
- Load power factor
- 0.85
- Cable reactance
- 0.08 Ω/km
- Permitted drop
- 4 %
Default results
- Voltage drop
- 4.31 V
- Percentage drop
- 1.04 %
- Entered limit
- Within entered limit