Voltage drop

Estimate feeder voltage drop from resistance, reactance and power factor, using your chosen voltage-drop limit.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • ΔV = √3 × I × L × (R cosφ + X sinφ). L is one-way length.
  • Indicative hot conductor resistivity: 0.02193 Ω·mm²/m; R = 0.4386 Ω/km; X = 0.08 Ω/km.
  • Maximum length at the entered limit: 231 m.

Before using the result

  • Use manufacturer resistance and reactance for final design. The entered supply voltage must match the phase arrangement; this estimate does not cover starting transients or unbalanced circuits.

Worked example

Illustrative default inputs. Enter your project values above.

Load current
100 A
One-way cable length
60 m
Conductor size
50 mm²
Supply voltage
415 V
Supply arrangement
Three phase — balanced
Conductor material
Copper
Insulation
XLPE — 90 °C
Load power factor
0.85
Cable reactance
0.08 Ω/km
Permitted drop
4 %

Default results

Voltage drop
4.31 V
Percentage drop
1.04 %
Entered limit
Within entered limit