Estimate the initial symmetrical fault current at transformer terminals from its rating and impedance.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • Isc ≈ rated current × 100 / impedance (%).
  • Assumes an infinite upstream source at nominal voltage. Feeder impedance, motor contribution, tolerances and voltage factors are not included.

Before using the result

  • This approximation is not a full IEC 60909 study. It does not calculate peak current, downstream fault level or certify switchgear breaking capacity. Obtain utility and manufacturer data for the final study.

Worked example

Illustrative default inputs. Enter your project values above.

Transformer rating
1000 kVA
Nameplate impedance
5 %
Supply voltage
415 V
Supply arrangement
Three phase — balanced

Default results

Transformer rated current
1,391.2 A
Terminal fault estimate
27.82 kA
Calculation location
Transformer terminals

Choose a reference or send your BOQ

Compare relevant product families, then confirm the exact rating, control supply and duty. Price and availability are confirmed with your enquiry.

Send a BOQ for quotationDiscuss the application

Technical references

These references support planning. The exact model documentation and a project-specific engineering review govern the final specification.