MCB / MCCB / ACB sizing
Find a nominal current candidate using your design load, cable capacity and manufacturer correction factor.
Enable JavaScript for live calculations. Read the method and default example below.
Method and assumptions
- Candidate current only. For an adjustable breaker use the relevant protective setting and manufacturer coordination data.
- Trip curve, poles, frame, Icu/Ics, overload characteristic and selectivity are not selected automatically.
- Also verify the device conventional operating current condition (I2 ≤ 1.45 Iz), starting conditions and disconnection time.
Before using the result
- Do not choose an MCB, MCCB or ACB solely by current. Confirm fault level and ratings at the actual operating voltage.
Worked example
Illustrative default inputs. Enter your project values above.
- Design load value
- 160
- Load unit
- Amps
- Supply arrangement
- Three phase — balanced
- Supply voltage
- 415 V
- Power factor for kW conversion
- 0.85
- Corrected cable capacity (Iz)
- 250 A
- Manufacturer current-rating factor
- 1
- Prospective fault level
- 25 kA
Default results
- Design current (Ib)
- 160 A
- Nominal current candidate
- 160 A
- Cable capacity check
- Ib ≤ In ≤ Iz