MCB / MCCB / ACB sizing

Find a nominal current candidate using your design load, cable capacity and manufacturer correction factor.

Enable JavaScript for live calculations. Read the method and default example below.

Method and assumptions

  • Candidate current only. For an adjustable breaker use the relevant protective setting and manufacturer coordination data.
  • Trip curve, poles, frame, Icu/Ics, overload characteristic and selectivity are not selected automatically.
  • Also verify the device conventional operating current condition (I2 ≤ 1.45 Iz), starting conditions and disconnection time.

Before using the result

  • Do not choose an MCB, MCCB or ACB solely by current. Confirm fault level and ratings at the actual operating voltage.

Worked example

Illustrative default inputs. Enter your project values above.

Design load value
160
Load unit
Amps
Supply arrangement
Three phase — balanced
Supply voltage
415 V
Power factor for kW conversion
0.85
Corrected cable capacity (Iz)
250 A
Manufacturer current-rating factor
1
Prospective fault level
25 kA

Default results

Design current (Ib)
160 A
Nominal current candidate
160 A
Cable capacity check
Ib ≤ In ≤ Iz

Choose a reference or send your BOQ